What temperature sensors should I specify for an AHU?

Temperature Sensor Specification for Air Handling Units

Specifying the right temperature sensors for an air handling unit (AHU) is more than selecting a sensor type — it requires careful attention to placement, accuracy class, time constant, and environmental protection. A poorly placed or incorrectly specified sensor can undermine the most sophisticated control sequence.

### Essential Sensor Positions

Every AHU requires at minimum four temperature measurement points. The **outdoor air temperature sensor** must be an NTC thermistor or Pt1000 RTD rated for -40°C to 60°C, mounted in a naturally aspirated or fan-aspirated solar radiation shield on the north-facing building elevation. Without a shield, direct solar radiation can introduce errors of 5–8°C, completely corrupting economiser changeover decisions and free cooling availability calculations.

The **mixed air temperature sensor** must be an averaging type — a flexible capillary or multiple-point sensor spanning the full duct cross-section downstream of the mixing box. Stratification in the mixed air plenum is common, especially when outdoor and return air temperatures differ by more than 10°C. A single-point sensor in a stratified mixed air stream can read 3–5°C above or below the true average, leading to incorrect coil staging and potential freeze risk.

The **supply air temperature sensor** is the most critical for control. It must be positioned at least 3–4 duct diameters downstream of the last coil to ensure complete mixing, and installed in a thermowell if the airstream may carry condensate or moisture. Platinum RTDs (Pt1000, Class A, ±0.15°C at 0°C) are preferred over thermistors for supply air because they maintain calibration across the full operating range without drift — essential when the sensor drives economiser, cooling, and heating sequences.

The **return air temperature sensor** can be a standard room or duct-mount sensor, typically located in the main return duct or ceiling plenum before the return fan. In buildings with multiple return paths, an averaging sensor array may be warranted.

### Accuracy and Time Constant

Per ASHRAE Guideline 36, all AHU temperature sensors should have a time constant of less than 30 seconds to ensure the control loop can respond to real process changes rather than lagged readings. Sensor accuracy should be ±0.3°C or better at the control setpoint — typically 12–13°C for supply air in VAV systems. Regular calibration verification against a certified reference thermometer should be part of the annual preventative maintenance schedule.

AHU Temperature Sensor Specification Guide

Recommended sensor types, accuracy, and placement requirements for each AHU temperature measurement location.

Sensor LocationRecommended TypeAccuracy RequirementMounting RequirementAdditional Protection
Outdoor AirPt1000 RTD or NTC thermistor±0.3°CSolar radiation shield, north-facingWeatherproof enclosure IP65 minimum
Mixed AirAveraging capillary (6–12 m)±0.5°CFull duct cross-section coverageNone — internal to AHU
Supply AirPt1000 RTD Class A±0.15°C at 0°CThermowell, 3–4 duct diameters downstream of coilCondensate-proof connection head
Return AirPt1000 or NTC 10k Type II±0.3°CReturn duct or ceiling plenumPerforated guard if in occupied space
Preheat Discharge (optional)Pt1000 RTD±0.2°CImmediately downstream of preheat coilHigh-temperature rated to 80°C

🔑 Key Takeaways

  • Outdoor air sensors require aspirated solar radiation shields mounted on north-facing elevations; unshielded sensors can read 5–8°C high in direct sun.
  • Mixed air sensors must be averaging types spanning the full duct cross-section — single-point sensors cannot detect stratification.
  • Supply air sensors should be Pt1000 RTDs with ≤30-second time constant, installed 3–4 diameters downstream of the last coil in a thermowell.
  • Sensor accuracy of ±0.3°C or better at the control setpoint is essential for stable economiser and coil staging sequences per Guideline 36.
  • Annual calibration verification against a certified reference should be part of the preventative maintenance programme.
Share:XLinkedIn