What is ASHRAE Guideline 36 and how does it improve HVAC control sequences?

ASHRAE Guideline 36 — The Standard for High-Performance HVAC Sequences

ASHRAE Guideline 36 represents a paradigm shift in HVAC controls design — moving from custom, programmer-dependent sequences that vary wildly in quality to standardised, peer-reviewed sequences that deliver consistent, verifiable energy performance. First published in 2018 and updated in 2021, it has rapidly become the most consequential HVAC controls document since the BACnet standard.

### The Trim-and-Respond Philosophy

The guideline's central innovation is the trim-and-respond control methodology, which replaces arbitrary fixed setpoints with algorithms that continuously seek the most energy-efficient operating point. Unlike traditional PID loops that control to a fixed setpoint, trim-and-respond sequences:

1. Continuously poll all zones to determine which is most demanding

2. Trim the setpoint (static pressure, supply air temperature, etc.) in small increments toward a more efficient value 3. Respond by reversing direction when any zone indicates it is approaching a deficit 4. Result: the system operates at exactly the minimum energy state that satisfies all zones

This approach is applied to duct static pressure reset (Section 5.3), supply air temperature reset (Section 5.5), zone temperature setpoint adjustment, and chilled water plant control.

### Standardised Sequences Covered

The 2021 edition provides complete, implementation-ready sequences for:

  • Variable Air Volume (VAV) air handling systems (the most detailed section)
  • Single-zone AHUs and rooftop units
  • Fan coil units
  • Chilled water plant control, including sequencing and reset strategies
  • Heating water plant control
  • Zone-level VAV terminal unit control

    Each sequence is documented with logic diagrams, setpoint tables, and tuning parameters — sufficient for a competent DDC programmer to implement without interpretation or improvisation.

    ### Code Mandate and Industry Adoption

    ASHRAE 90.1-2019 Section 6.4.3.10 now mandates that DDC systems comply with Guideline 36 for many building types, effectively elevating the guideline to code status. Major BMS manufacturers have responded by developing Guideline 36-compliant application libraries:

    - JCI Metasys: G36 Application Library with pre-engineered control programs

  • Siemens Desigo: Guideline 36 Standard Application packages
  • Schneider Electric EcoStruxure: SmartX AS-P Guideline 36 programs
  • Honeywell: Optimizer Suite with G36 compliance mode

    These pre-built libraries reduce commissioning time by 40–60% compared to custom-programmed sequences and eliminate the programming errors that plague bespoke DDC implementations.

    ### Australian Adoption

    In Australia, Guideline 36 is increasingly referenced in project specifications, particularly for Green Star and NABERS-rated buildings where energy performance is independently verified. The trim-and-respond methodology aligns well with the NCC Section J performance requirements, and several Australian controls contractors now offer Guideline 36-compliant programming as a standard service offering.

  • ASHRAE Guideline 36-2021 Key Sequences Summary

    Major control sequences defined in Guideline 36 with their primary energy impact mechanisms and the trim-and-respond parameters used.

    SequenceSectionPrimary Energy MechanismTrim ParameterRespond Trigger
    Duct Static Pressure Reset5.3Fan speed reduction (cube law)Duct static pressure setpoint (-0.05 in. w.g.)Any VAV damper > 90% open
    Supply Air Temperature Reset5.5Chiller lift reduction; economiser hoursSAT setpoint (+0.2°F)Any zone above cooling setpoint
    Zone Temperature Setpoint5.9Heating/cooling load reductionZone setpoint towards ambientOccupant override or demand
    Economiser Changeover5.4Free cooling vs mechanicalChangeover setpointOA conditions vs return air
    Chilled Water Plant Reset6.0Chiller lift reductionCHW supply temp (+0.5°F)Any valve > 90% open
    Heating Water Plant Reset7.0Boiler efficiency improvementHW supply temp (-0.5°F)Any valve approaching closed

    🔑 Key Takeaways

    • ASHRAE Guideline 36's trim-and-respond methodology replaces fixed setpoints with continuous optimisation, proven to reduce HVAC energy by 30–50%
    • The 2021 edition covers VAV AHUs, single-zone units, fan coil units, and central plant control with complete implementation-ready logic diagrams
    • ASHRAE 90.1-2019 mandates Guideline 36 compliance for many building types, elevating the guideline to de facto code status
    • Major BMS manufacturers now provide Guideline 36-compliant program libraries that reduce commissioning time by 40–60% and eliminate programming errors
    • For Australian Green Star and NABERS projects, specifying Guideline 36 sequences provides a verifiable path to demonstrated energy performance
    Share:XLinkedIn